This project requires the design and installation of an automatic fire sprinkler system for a tenant improvement in an existing Group M and M occupancy building. The system must comply with the 2018 IBC, IFC, and 2019 NFPA 13 standards, providing specified minimum water density and sprinkler spacing based on hazard classification. New pendent sprinklers will be installed in the new ceiling grid to meet code requirements and ensure adequate fire protection.
This project involves the design and installation of an automatic fire sprinkler system in an existing Group M and M occupancy building as part of a tenant improvement. The sprinkler system shall be designed and installed in accordance with the 2018 International Building Code (IBC), 2018 International Fire Code (IFC), and the 2019 edition of NFPA 13. The design for the Group M occupancy area must provide a minimum density of 0.20 gallons per minute per square foot over 1,500 square feet, as specified by NFPA 13. New pendent sprinklers will be added to the new ceiling grid. The maximum allowable spacing for pendent sprinklers shall be 225 square feet for light hazard areas and 130 square feet for Ordinary Hazard Group 1 and Group 2 occupancy areas. All work must comply with applicable codes and standards to ensure proper fire protection coverage and system performance.